Fike Twinflex Multipoint ASD Detector with Sounder, Smoke+Heat, 2‑Wire, 204-0001

MultiSensor
Twinflex ASD Detector with Sounder
About this product

Fike 204-0001 Twinflex Multipoint ASD Detector with integral sounder. A 2‑wire, plug‑in multi‑criteria detector that combines a photo‑electric (optical scatter) smoke chamber with a thermistor heat sensor. Configurable via on‑board DIP switches for smoke, heat or combined operation. Designed for use with Fike Twinflex / Twinflex Pro panels and provides an integrated audible warning without separate sounder wiring.

  • Multi‑criteria detection: photo‑electric + thermistor heat sensor; selectable modes.
  • Integral sounder (204‑0001 variant) – selectable sound patterns/volume via DIP switches.
  • 2‑wire Twinflex protocol compatible — no extra wiring for the sounder.
  • Self‑calibrates periodically (approx. every 6 hours) with continuous contamination monitoring.
  • Tamper‑resistant head and removal tool for secure maintenance at height.
  • Compact ceiling mounting: 107 mm diameter × 75 mm height — indoor use.

Compliance & installation: Declared compliant with applicable EN54 parts per Fike Declaration of Performance (DoP). Always follow the Fike installation manual and the DoP for panel loading, DIP switch settings, and siting guidance. For system design and regulatory labelling (IP rating, measured sound level, device loading figures) use the manufacturer technical datasheet as the authoritative source.

Safety: Installation must be carried out by a competent electrical/fire installer in accordance with local regulations and the Fike installation instructions. Verify system compatibility with Twinflex / Twinflex Pro control equipment prior to installation.

FAST delivery by Order within
Ships from United Kingdom
Secure payment transactions
Add a WME Product Care Plan Includes warranty, replacement and repairs backed by WME
Why add a product care plan:
  • Full breakdown support
  • Full replacement if we can't repair your product within 10 days
  • All parts, labour and callouts included if necessary
  • Extended manufacturer warranty with faster turn arounds
  • Excludes accidental & cosmetic damages
By selecting one of these plans you agree to purchase WME Care Plan. Please read the Terms and Important information to ensure WME Care Plan is right for you. Compare prices of extended warranties for electrical goods at www.compareextendedwarranties.co.uk
WME Care
Technical Details
Specifications
General
Model
Fike 204-0001 (Twinflex MP ASD with sounder)
Device type
2‑wire Twinflex multipoint ASD detector (photoelectric + thermistor)
Intended panels
Twinflex / Twinflex Pro
Mechanical
Dimensions
107 mm diameter × 75 mm height
Mounting
Plug‑in detector head; tamper‑resistant removal
Location
Indoor use
Electrical
Operating voltage
18–32 V DC
Quiescent current
56 µA (typical)
Sounder current
Sounder High ≈ 8 mA; Sounder Low ≈ 2.5 mA (typical, see manual)
Environmental-&-performance
Operating temperature
-10 °C to +50 °C
Self‑calibration
Automatic (approx. every 6 hours) with continuous contamination monitoring
Sound output
Approx. 70–90 dB(A) (reseller listings; verify with Fike for certified figures)
Ingress protection
INSUFFICIENT DATA
Compliance-&-standards
Standards
Declared to applicable EN54 parts (see Fike DoP: EN54‑3, EN54‑5, EN54‑7 as referenced)
Technical data
Device loading / SLU/DLU figures documented in Fike technical manual
Installation-&-indicators
LED behaviour
Flash patterns for normal, fault, contamination and alarm (see manual)
Configuration
On‑board DIP switches for detection mode, EOL selection and sound pattern/volume

Specifications

General

Model Fike 204-0001 (Twinflex MP ASD with sounder)
Device type 2‑wire Twinflex multipoint ASD detector (photoelectric + thermistor)
Intended panels Twinflex / Twinflex Pro

Mechanical

Dimensions 107 mm diameter × 75 mm height
Mounting Plug‑in detector head; tamper‑resistant removal
Location Indoor use

Electrical

Operating voltage 18–32 V DC
Quiescent current 56 µA (typical)
Sounder current Sounder High ≈ 8 mA; Sounder Low ≈ 2.5 mA (typical, see manual)

Environmental-&-performance

Operating temperature -10 °C to +50 °C
Self‑calibration Automatic (approx. every 6 hours) with continuous contamination monitoring
Sound output Approx. 70–90 dB(A) (reseller listings; verify with Fike for certified figures)
Ingress protection INSUFFICIENT DATA

Compliance-&-standards

Standards Declared to applicable EN54 parts (see Fike DoP: EN54‑3, EN54‑5, EN54‑7 as referenced)
Technical data Device loading / SLU/DLU figures documented in Fike technical manual

Installation-&-indicators

LED behaviour Flash patterns for normal, fault, contamination and alarm (see manual)
Configuration On‑board DIP switches for detection mode, EOL selection and sound pattern/volume

Twinflex ASD Detector with Sounder features

Fike 204-0001 Twinflex ASD Detector with Sounder

Fike Twinflex Multipoint ASD Detector with Sounder, Smoke+Heat, 2‑Wire, 204-0001

Introduction: Meet the Fike Twinflex 204-0001 Multipoint ASD Detector with Sounder

Fike Twinflex Multipoint ASD Detector with Sounder, Smoke+Heat, 2‑Wire, 204-0001is a compact, plug-in multi-criteria detector designed for modern two‑wire Twinflex fire alarm systems. Combining a photo‑electric (optical scatter) smoke chamber with a thermistor heat sensor, this detector is configurable for smoke, heat or combined operation via on‑board DIP switches. The 204-0001 variant adds an integral audible sounder, giving installers an option to deliver local warning without separate sounder wiring. Declared compliant with applicable EN54 parts per Fike Declaration of Performance, the Twinflex ASD detector is aimed at installers and specifiers who need reliable, low‑impact detection for indoor environments.

Key features at a glance

  • Multi‑criteria detection:Photo‑electric sensor plus thermistor heat element for accurate detection and fewer false alarms.
  • Integral sounder (204‑0001):Built‑in audible warning with selectable patterns and volume via DIP switches.
  • 2‑wire Twinflex compatibility:Plug‑in design and communication over the Twinflex protocol — no extra wiring for the sounder.
  • Automatic self‑calibration:Periodic calibration (approx. every six hours) with continuous contamination monitoring for stable long‑term performance.
  • Installer friendly:Tamper‑resistant head and removal tool reduce maintenance issues at height; small ceiling footprint (107 mm × 75 mm).

Detailed specifications and benefits

The Twinflex 204-0001 is compact and designed for conventional ceiling mounting. Its dimensions (107 mm diameter × 75 mm height) and plug‑in mounting style make it quick to fit in standard detector bases. A tamper‑resistant head and dedicated removal tool help prevent accidental removal or tampering, particularly useful in public or high‑traffic spaces.

Operating across 18–32 V DC and drawing minimal quiescent current (approx. 56 µA), the detector is energy efficient and suitable for centralized Twinflex systems. The integral sounder has low additional current draw (typical high ≈ 8 mA; low ≈ 2.5 mA), which means the device can provide local audible warning without requiring a separate power circuit for a sounder — simplifying wiring and panel loading considerations. On‑board DIP switches allow configuration of detection mode (smoke, heat, or combined), end‑of‑line options, and sound pattern/volume.

Combining an optical scatter chamber with a thermistor heat sensor provides two complementary detection methods: the photoelectric element is sensitive to smoldering and visible particle smoke, while the thermistor reliably detects a rise in temperature associated with fast‑burning fires. This multi‑criteria approach reduces false alarms — common in areas with dust or steam — while maintaining sensitivity to genuine fire conditions.

Automatic self‑calibration every six hours and continuous contamination monitoring help maintain consistency over time. Instead of forcing frequent manual recalibrations, the detector adapts to slow changes in chamber contamination, providing more stable thresholds for alarm and fault reporting.

Fike declares the unit to applicable EN54 parts (see Fike Declaration of Performance for details such as EN54‑3, EN54‑5, EN54‑7 references). Installers should always follow the Fike installation manual and the DoP for system loading, DIP switch selection and siting guidance. The manufacturer technical datasheet remains the authoritative source for device loading figures (SLU/DLU), measured sound output, and IP rating considerations. Installation must be carried out by a competent installer and verified against local regulations.

Where the 204-0001 excels: use cases and scenarios

  • Offices and commercial interiors:In office buildings, the combined smoke and heat sensing reduces false alarms caused by everyday activities while providing reliable detection. The integrated sounder saves on ceiling space and simplifies wiring.
  • Retail and shopping centres:Retail units often require discreet detection with dependable alarm signaling. The small footprint and tamper‑resistant head help maintain aesthetics while protecting the device from accidental removal.
  • Educational facilities:Schools and universities benefit from the integral sounder which provides localized audible warnings without extra cabling — useful in retrofit projects.
  • Healthcare and assisted living:Multi‑criteria detection helps differentiate nuisance sources (e.g., steam from showers, cooking) from real threats; the self‑calibration and contamination monitoring reduce ongoing maintenance needs.
  • Small industrial/warehouse offices:Where environmental contaminants exist but early warning is required, the selectable modes and robust detection help tailor performance to the environment.

How it compares with other detector options

Single‑criteria detectors are simpler and sometimes cheaper, but they can be more prone to nuisance triggers or slower to detect certain fire types. The Twinflex 204-0001’s combined smoke + heat approach balances sensitivity and specificity: it picks up both smoldering (photoelectric) and rapid heat rises (thermistor), reducing false alarms while maintaining early warning.

Traditional approaches often pair a detector head with a separate sounder device. While that can allow louder or differently located notification appliances, it requires extra wiring, mounts and panel outputs. The 204-0001 eliminates the need for separate sounder wiring when used on Twinflex systems, reducing installation time and material costs, and simplifying panel loading calculations. For projects where highly directional or high‑SPL notification is required, a separate sounder may still be preferable.

Many manufacturers offer multiparameter detectors with integrated sounders. Key differentiators are compatibility and system integration. The Twinflex 204-0001 is specifically designed for Twinflex / Twinflex Pro panels using the Twinflex protocol; this makes it a straightforward choice for projects already using those control panels. Other brands may offer broader protocol compatibility or additional features (e.g., remote test, dual‑LED indicators, larger SPL ratings), so the right choice depends on the control system, required certification details and specific project constraints.

Customer feedback and real‑world impressions

No verified customer testimonials were provided with the product brief. However, based on typical installer and reseller feedback for detectors in this class, common positives and considerations tend to include:

  • Positives typically reported:Easy plug‑in installation, reliable multi‑criteria detection, low quiescent current and the convenience of an integrated sounder that avoids extra wiring on Twinflex systems.
  • Practical considerations:Installers often verify sound output levels on site against room requirements (the reseller listing suggests approx. 70–90 dB(A), but the certified figure should be checked in Fike documentation). Also recommended is careful DIP switch configuration during commissioning to match detection behaviour to the protected environment.

For authoritative performance and system behaviour, installers rely on the Fike technical manual, Declaration of Performance and site‑specific commissioning checks.

Comparative purchasing considerations and pricing

The Fike 204-0001 represents a cost‑effective solution for projects that standardize on Twinflex panels. The suggested retail price (as supplied) is approximately 41.99 (cost price shown as 35.05), which places it competitively against other integrated sounder multipoint detectors. When comparing price, factor in reduced labor and materials from not having to add separate sounder wiring and the lower ongoing maintenance overhead thanks to self‑calibration features.

Conclusion: Why choose the Fike Twinflex 204-0001?

The Fike Twinflex 204-0001 Multipoint ASD Detector with integral sounder is a practical, installer‑friendly detector that blends multi‑criteria detection with an onboard audible device for straightforward Twinflex system installations. Its compact form, tamper‑resistant design and automated calibration combine to reduce maintenance and nuisance alarms, while DIP switch configurability provides flexibility for diverse indoor environments. For projects using Twinflex or Twinflex Pro control panels where simplifying wiring and preserving ceiling aesthetics are priorities, the 204-0001 is a sensible choice. As with all life‑safety equipment, ensure proper system design, commissioning and verification against the Fike technical documentation and local regulations prior to installation.

Fike 204-0001 Twinflex ASD Detector with Sounder
Dynamic CCTV New

Fike Twinflex Multipoint ASD Detector with Sounder, Smoke+Heat, 2‑Wire, 204-0001

£31.25 £37.97

Fike 204-0001 Twinflex Multipoint ASD Detector with integral sounder. A 2‑wire, plug‑in multi‑criteria detector that combines a photo‑electric (optical scatter) smoke chamber with a thermistor heat sensor. Configurable via on‑board DIP switches for smoke, heat or combined operation. Designed for use with Fike Twinflex / Twinflex Pro panels and provides an integrated audible warning without separate sounder wiring.

Compliance & installation: Declared compliant with applicable EN54 parts per Fike Declaration of Performance (DoP). Always follow the Fike installation manual and the DoP for panel loading, DIP switch settings, and siting guidance. For system design and regulatory labelling (IP rating, measured sound level, device loading figures) use the manufacturer technical datasheet as the authoritative source.

Safety: Installation must be carried out by a competent electrical/fire installer in accordance with local regulations and the Fike installation instructions. Verify system compatibility with Twinflex / Twinflex Pro control equipment prior to installation.