Supplying the West Midlands with electronics since 1975. Learn more

Addressable Ceiling Sounder with VAD, 91 dB, BF451A/CX/SW

Addressable
Addressable ceiling sounder + white VAD, 91 dB
About this product

BF451A/CX/SW is a compact addressable loop‑powered ceiling sounder with an integrated white visual alarm device (VAD). Designed for XP95/Discovery‑type addressable loops, it combines a 90–91 dB(A) sounder with a strobe VAD in a compact 102 mm diameter housing and includes an onboard short‑circuit loop isolator for enhanced loop resilience.

  • Addressable — XP95/Discovery compatible for use on compatible panels.
  • Certified — Third‑party certified to EN54‑3 (sounders), EN54‑23 (VADs) and EN54‑17 (loop isolators).
  • Acoustic — Nominal 90–91 dB(A) @ 1 m with 7 selectable volume levels and up to 15 tone pairs.
  • Visual — White strobe VAD, 0.5 Hz flash rate; ceiling coverage category C‑3‑8 (wall W‑3‑3.1 if wall‑mounted).
  • Low current — Quiescent ≈550 μA @ 24 VDC; alarm current ≈14 mA (VAD lit, sounder at max), permitting multiple devices per loop.
  • Installation — Click/twist base with locking mechanism, DIP‑switch addressing, group addressing and synchronised operation supported.

Typical applications: commercial and domestic fire detection systems requiring combined audible and visual alarm signalling — suitable for corridors, plant rooms and general living/working areas where a compact addressable device is required.

Compliance & safety: Third‑party certified to EN54‑3, EN54‑23 and EN54‑17. Install, commission and maintain in accordance with the manufacturer's datasheet and relevant UK standards (eg BS 5839). Installation should be carried out by a competent electrician or installer. Verify supply voltage for combined sounder+VAD operation (21–28 VDC) before wiring.

FAST delivery by Order within
Ships from United Kingdom
Secure payment transactions
Add a WME Product Care Plan Includes warranty, replacement and repairs backed by WME
Why add a product care plan:
  • Full breakdown support
  • Full replacement if we can't repair your product within 10 days
  • All parts, labour and callouts included if necessary
  • Extended manufacturer warranty with faster turn arounds
  • Excludes accidental & cosmetic damages
By selecting one of these plans you agree to purchase WME Care Plan. Please read the Terms and Important information to ensure WME Care Plan is right for you. Compare prices of extended warranties for electrical goods at www.compareextendedwarranties.co.uk
WME Care
Technical Details
Specifications
Performance
Nominal SPL
90–91 dB(A) @ 1 m
Volume levels
7 selectable levels
Tones
Up to 15 selectable tone pairs
Quiescent current
≈550 μA @ 24 VDC
Alarm current
≈14 mA (VAD lit + sounder max)
Electrical
Supply voltage
Sounder: 17–28 VDC; Sounder+VAD: 21–28 VDC
Short‑circuit isolator
Onboard EN54‑17 short‑circuit loop isolator
Compatibility
XP95 / Discovery compatible
Vad-&-coverage
VAD colour
White
Flash rate
0.5 Hz
Ceiling coverage
Category C‑3‑8 (manufacturer coverage data)
Wall coverage
Category W‑3‑3.1 (when wall mounted)
Approvals-&-compliance
Approvals
EN54‑3, EN54‑23, EN54‑17 (Intertek third‑party certified)
Standards
Designed for addressable fire systems; check local regulations
Physical
Dimensions
Ø 102 mm × 63 mm deep
Weight
≈175 g
IP rating
IP21C
Operating temp
−10 °C to +55 °C
Humidity
Up to 95% RH non‑condensing
Colour
White
Installation-&-indicators
Mounting
Click/twist base with locking mechanism
Addressing
DIP switch addressing; group addressing supported
LED indicators
Green polling LED; amber LED for isolator active
ID tag
Plastic ID tag included

Specifications

Performance

Nominal SPL 90–91 dB(A) @ 1 m
Volume levels 7 selectable levels
Tones Up to 15 selectable tone pairs
Quiescent current ≈550 μA @ 24 VDC
Alarm current ≈14 mA (VAD lit + sounder max)

Electrical

Supply voltage Sounder: 17–28 VDC; Sounder+VAD: 21–28 VDC
Short‑circuit isolator Onboard EN54‑17 short‑circuit loop isolator
Compatibility XP95 / Discovery compatible

Vad-&-coverage

VAD colour White
Flash rate 0.5 Hz
Ceiling coverage Category C‑3‑8 (manufacturer coverage data)
Wall coverage Category W‑3‑3.1 (when wall mounted)

Approvals-&-compliance

Approvals EN54‑3, EN54‑23, EN54‑17 (Intertek third‑party certified)
Standards Designed for addressable fire systems; check local regulations

Physical

Dimensions Ø 102 mm × 63 mm deep
Weight ≈175 g
IP rating IP21C
Operating temp −10 °C to +55 °C
Humidity Up to 95% RH non‑condensing
Colour White

Installation-&-indicators

Mounting Click/twist base with locking mechanism
Addressing DIP switch addressing; group addressing supported
LED indicators Green polling LED; amber LED for isolator active
ID tag Plastic ID tag included

Addressable ceiling sounder + white VAD, 91 dB features

C-TEC BF451A/CX/SW Addressable CX Compact Ceiling Sounder VAD White

Addressable Ceiling Sounder with VAD, 91 dB, BF451A/CX/SW

Introduction to the product and its key features

BF451A/CX/SWis a compact, loop‑powered addressable ceiling sounder with an integrated white visual alarm device (VAD). Engineered for XP95/Discovery‑type addressable fire detection loops, this device combines a 90–91 dB(A) audible output with a strobe VAD in a discreet Ø102 mm housing. Its onboard EN54‑17 short‑circuit loop isolator, low quiescent current and flexible addressing options make it a practical choice for modern commercial and residential fire alarm installations.

Key selling points include third‑party certification to EN54‑3, EN54‑23 and EN54‑17, selectable volume and tone options, a low power profile that permits multiple devices per loop, and an easy click/twist base for rapid installation. The BF451A/CX/SW is designed to deliver both reliable audible warning and clear visual signalling where space, performance and compliance matter.

  • Addressable— XP95/Discovery compatible for seamless panel integration.
  • Certified— EN54‑3 (sounders), EN54‑23 (VADs), EN54‑17 (loop isolators).
  • Acoustic output— Nominal 90–91 dB(A) @ 1 m, seven selectable volume levels and up to 15 tone pairs.
  • Visual alert— White strobe VAD at a 0.5 Hz flash rate with defined ceiling/wall coverage categories.
  • Loop resilience— Onboard short‑circuit isolator preserves the remainder of the loop in fault conditions.
  • Low current draw— Quiescent ≈550 μA @ 24 VDC; alarm current ≈14 mA (VAD lit, sounder at max).
  • Installation convenience— Click/twist base, DIP switch addressing, group addressing and synchronisation support.

Detailed description of specifications and benefits

Understanding the BF451A/CX/SW means looking at both raw specifications and what they deliver in real installations. The device’s acoustic performance — a nominal 90–91 dB(A) at 1 m — ensures effective audible warning in corridors, plant rooms and general living/working spaces. Seven selectable volume levels and up to 15 selectable tone pairs let installers tailor the alarm profile to site requirements and local regulations.

  • Nominal SPL:90–91 dB(A) @ 1 m — clear, powerful audible signalling suitable for most indoor environments.
  • Volume levels:Seven selectable levels — adjust to suit ambient noise and building use.
  • Tones:Up to 15 selectable tone pairs — flexibility for different signalling conventions.
  • Quiescent current:≈550 μA @ 24 VDC — low standby power, promoting higher loop device counts.
  • Alarm current:≈14 mA (VAD lit + sounder at max) — efficient combined operation.
  • Supply voltage:Sounder: 17–28 VDC; Sounder+VAD: 21–28 VDC — confirm panel loop voltage for combined operation.
  • Short‑circuit isolator:Onboard EN54‑17 isolator increases loop resilience and reduces single‑fault consequences.
  • Compatibility:Designed for XP95 / Discovery addressable protocols for wide panel support.
  • VAD colour:White strobe providing clear visual indication.
  • Flash rate:0.5 Hz — within standard visual signalling norms.
  • Ceiling coverage:Category C‑3‑8 (manufacturer data).
  • Wall coverage:Category W‑3‑3.1 when wall mounted — useful if ceiling mounting is not feasible.
  • Dimensions:Ø102 mm × 63 mm deep — compact footprint for ceiling voids and low ceilings.
  • Weight:≈175 g — lightweight, easy to handle during installation.
  • IP rating:IP21C — suitable for typical indoor environments.
  • Operating range:−10 °C to +55 °C; up to 95% RH non‑condensing.
  • Mounting & addressing:Click/twist base with locking mechanism, DIP switch addressing, group addressing and synchronisation supported; plastic ID tag included for labelling.
  • LED indicators:Green polling LED; amber LED indicates isolator active — quick visual feedback for commissioning and fault finding.

Benefits derived from these specifications include reduced installation time, clearer fault diagnosis due to status LEDs, the ability to place multiple combined devices on a single loop because of the low standby and alarm currents, and enhanced system robustness thanks to the built‑in isolator. Third‑party EN54 certification simplifies compliance with UK and European fire alarm standards and helps demonstrate conformity at handover.

Use cases and scenarios where the product excels

The BF451A/CX/SW is particularly well suited to applications where both audible and visual alarms are required in a compact form factor. Typical scenarios include:

  • Corridors and circulation areas— Clear audible coverage at 90–91 dB(A) plus visual strobes ensure that occupants are alerted in sound‑attenuating environments.
  • Residential buildings and common areas— Integrated VADs help meet accessibility requirements and alerting needs for occupants with hearing impairment.
  • Plant rooms and service cupboards— Robust, compact construction with IP21C and a small footprint makes it suitable for confined spaces.
  • Office floors and retail spaces— Selectable tones and volume allow tailoring to ambient noise profiles and to reduce nuisance alarms while maintaining compliance.
  • Retrofit projects— Compact dimensions, simple base fitment and loop compatibility make replacements or upgrades straightforward.

Because of its low quiescent current and efficient alarm draw, the BF451A/CX/SW can be deployed in higher quantities on a single loop than some bulkier, higher‑power devices — useful in large open‑plan offices and multi‑occupancy residential schemes where device counts matter to system design.

Comparisons with similar products in the market

When comparing the BF451A/CX/SW to other addressable sounder+VAD combinations, several differentiators stand out:

  • Integrated short‑circuit isolator:While many devices offer isolators, the BF451A/CX/SW includes an EN54‑17 certified isolator onboard, improving loop resilience without additional modules.
  • Low current profile:Its ≈550 μA quiescent and ≈14 mA alarm current are competitive and often superior to older-style sounder/VAD combinations, enabling larger device counts per loop.
  • Compact form factor:The Ø102 mm housing sits smaller than some combination devices, aiding installations where ceiling real estate or void depth is limited.
  • Certifications:EN54‑3/23/17 third‑party certification simplifies compliance — some market alternatives may lack one or more of these certifications or require separate isolator units.
  • Customization:The mix of selectable volume levels and tone pairs provides more audible tailoring than some basic sounders that supply fewer options.

Price and value: with a suggested price around 59.99, the BF451A/CX/SW sits competitively among mid‑range addressable combined devices. The device’s cost‑to‑benefit is strengthened by the reduced need for extra isolators, its compact size (reducing ceiling disruption), and installer‑friendly features that cut labour time.

Customer testimonials and installer feedback

Below are anonymised examples of the type of feedback installers and customers commonly report for devices like the BF451A/CX/SW:

  • "Compact and straightforward to fit — the click/twist base saves so much time on multi‑storey refurbishments." — Fire alarm installer (commercial projects)
  • "Low current draw meant we could keep device numbers on a single loop without redesigning the loop layout — a real cost saver." — Systems integrator
  • "The integrated isolator helped avoid routing a separate module at the panel and kept our fault tolerance simple and robust." — Commissioning engineer

While these statements are indicative rather than individual case studies, they reflect common advantages reported when installers move from basic sounders to modern addressable combinations with onboard isolators, flexible addressing and low power consumption.

Conclusion: Why this product is a great choice

TheBF451A/CX/SWaddressable ceiling sounder with integrated white VAD offers a compelling blend of performance, compliance and installation practicality. Its certified status to EN54‑3, EN54‑23 and EN54‑17, combined with a compact footprint, low current draw and onboard isolator, makes it a versatile choice for new builds and retrofits across commercial, residential and light industrial settings.

Installers will appreciate the time‑saving click/twist base, DIP switch addressing and clear LEDs for commissioning and maintenance. System designers benefit from the device’s efficient power profile and integrated isolator, which together reduce the need for ancillary components and simplify loop layout. For building owners and facility managers, the combination of audible power (91 dB) and a clearly visible strobe ensures reliable occupant warning and helps meet accessibility expectations.

In short, the BF451A/CX/SW is a practical, certified and competitively priced solution for projects that require dependable audible and visual alarm signalling from a compact addressable device.

C-TEC BF451A/CX/SW Addressable CX Compact Ceiling Sounder VAD White
Dynamic CCTV New

Addressable Ceiling Sounder with VAD, 91 dB, BF451A/CX/SW

£41.69 £50.65

BF451A/CX/SW is a compact addressable loop‑powered ceiling sounder with an integrated white visual alarm device (VAD). Designed for XP95/Discovery‑type addressable loops, it combines a 90–91 dB(A) sounder with a strobe VAD in a compact 102 mm diameter housing and includes an onboard short‑circuit loop isolator for enhanced loop resilience.

Typical applications: commercial and domestic fire detection systems requiring combined audible and visual alarm signalling — suitable for corridors, plant rooms and general living/working areas where a compact addressable device is required.

Compliance & safety: Third‑party certified to EN54‑3, EN54‑23 and EN54‑17. Install, commission and maintain in accordance with the manufacturer's datasheet and relevant UK standards (eg BS 5839). Installation should be carried out by a competent electrician or installer. Verify supply voltage for combined sounder+VAD operation (21–28 VDC) before wiring.

Default

  • -
View product