Introduction: What the Haydon EN54-4 Fire Alarm PSU Is and Why It Matters
Haydon HAY-PSUEN54-5Ais a boxed, EN54-4 certified uninterruptible power supply (PSU) designed specifically for fire-detection and life-safety systems. Delivering a nominal 27.6 V DC output with a continuous 5 A rating, the unit integrates a temperature-compensated battery charger, automatic mains-to-battery switchover and multiple protection features inside a tamper-protected steel enclosure. For installers, systems integrators and facilities managers, this type of PSU is a core component that ensures fire-alarm panels and associated devices remain powered and compliant with applicable safety standards during mains interruptions.
Key Features at a Glance
- EN54-4 certifiedfor fire-detection and alarm system use.
- 27.6 V DC outputwith a continuous 5 A rating suitable for small- to medium-sized fire alarm panels and devices.
- Built-in battery management:charger, automatic switchover and deep-discharge protection; typically supports 2 × 7 Ah SLA in the small enclosure variant.
- Tamper-protected steel enclosurewith mains, battery and fault LEDs and a tamper switch.
- Remote signalling:mains-fail / fault relay to integrate with building management or monitoring systems.
- Protections:electronic overload, short-circuit, mains transient and battery deep-discharge protection.
Detailed Specifications and the Benefits They Deliver
The HAY-PSUEN54-5A provides a nominal 27.6 V DC output with a continuous 5 A rating. This makes it well suited to a wide range of fire-alarm panels, notification devices and ancillary modules that require a stable DC supply. The mains input range (110–240 V AC, 47–63 Hz) allows flexibility for installations across regions with different supply standards.
The unit includes an onboard, temperature-compensated charger (typ. ~0.5 A) and is designed to accept typical small enclosure batteries such as 2 × 7 Ah sealed lead-acid (SLA) cells. Automatic mains-to-battery switchover ensures seamless power continuity during mains failures, while built-in deep-discharge protection helps preserve battery life and reliability so systems remain operational for required standby periods.
Front-panel LEDs indicate mains presence, battery condition and fault states, giving immediate local status. For remote monitoring and integration into building management or alarm-monitoring services, the PSU provides a mains-fail / fault relay output. A tamper (lid) switch and tamper-protected steel enclosure support secure installations where physical access must be restricted.
The HAY-PSUEN54-5A includes electronic overload and short-circuit protection as well as mains transient protection to safeguard both the PSU and connected equipment. These protections reduce the risk of nuisance trips, component damage and extended downtime—important considerations in life-safety systems where reliability is paramount.
Approximate dimensions for the small enclosure variant are 275 × 330 × 80 mm, though Haydon offers multiple enclosure variants depending on battery capacity requirements. The unit carries EN54-4 certification, a widely recognised standard for fire-detection power supplies in many territories. Confirm the exact enclosure variant, battery fitment and certification markings (e.g., UKCA/CE) from the datasheet before ordering and during installation.
Use Cases and Scenarios Where the PSU Excels
The HAY-PSUEN54-5A is aimed at installations that require a compact, certified power-source solution for fire-detection systems. Typical use cases include:
- Small commercial premises such as retail units, offices and small warehouses where a single fire-alarm panel and a limited number of devices need continuous, compliant power.
- Residential apartment blocks and multi-dwelling developments where common-area fire systems must meet regulatory standards and offer tamper protection.
- Schools, healthcare clinics and community centres needing a dependable backup supply for critical life-safety equipment.
- Refurbishment projects where an EN54-4 certified boxed PSU is required to replace legacy power units while meeting current standards.
- Systems integrators and installers who value a boxed solution with a ready-made enclosure, tamper switch and remote fault relay to streamline installation and commissioning.
Because the unit is EN54-4 certified, it is particularly valuable in jurisdictions or projects that demand certified components for compliance, insurance and inspection reasons. Note that this is not a plug-and-play consumer product: installation, wiring, and battery selection should be performed by a qualified engineer following EN54 guidance and local regulations.
How the Haydon Unit Compares with Similar Products
When evaluating fire-alarm PSUs, installers typically compare certification status, continuous current rating, battery capacity support, enclosure features and remote signalling options. Here are the main comparison points where the Haydon HAY-PSUEN54-5A stands out or is typical of the category:
- Certification:EN54-4 certification is a key differentiator versus generic or consumer-grade PSUs. Many lower-cost alternatives lack EN54-4 approval and therefore are not suitable for regulated fire-alarm installations.
- Output current:At 5 A continuous, the Haydon unit fits a common mid-range power requirement. Other PSUs are available with lower (1–3 A) or higher (10–20 A) ratings; choose based on total load and battery standby requirements.
- Enclosure and security:The tamper-protected steel enclosure and lid-switch are standard for professional boxed PSUs. Some minimalist or DIN-rail solutions trade off enclosure security for compactness, which may be unsuitable for public or high-security installations.
- Battery flexibility:The small enclosure variant supports typical 2 × 7 Ah SLA batteries. Larger PSUs or modular designs may accept bigger batteries or additional modules for extended standby times but at increased footprint and cost.
- Monitoring interfaces:The inclusion of a mains-fail / fault relay is common in professional PSUs; some competing models add programmable outputs, supervisory communications or networkable telemetry which are useful for central monitoring but come at higher cost and complexity.
- Price-to-feature balance:With a suggested price of 189.00 (suggested), the Haydon PSU sits in the value segment for certified boxed PSUs. Higher-end alternatives with expanded telemetry or larger current ratings typically command higher prices; lower-cost units often lack EN54-4 certification.
Customer Testimonials and Installer Feedback
There are no publicly supplied customer testimonials included with the product brief. In place of direct quotes, common feedback themes reported by installers and integrators for EN54-4 certified boxed PSUs of this class include reliability, ease of installation and compliance reassurance. Typical practical observations from professionals are:
- Appreciation for the ready-to-mount boxed format and pre-wired battery chamber that reduces onsite wiring time.
- Value placed on visible status LEDs and a dedicated fault relay for straightforward commissioning and remote monitoring integration.
- Requests for clarity on exact enclosure dimensions and battery fitment options prior to ordering—important when space behind panels or in plant rooms is constrained.
For accurate user reviews and performance reports, consult reseller pages, installer forums or request references from the supplier. Always confirm warranty and support arrangements directly with Haydon or your distributor; manufacturer warranty information was not supplied in the product brief.
Conclusion: Why the Haydon HAY-PSUEN54-5A Is a Strong Choice
The Haydon EN54-4 27.6 V 5 A PSU is a practical, certificated boxed power solution for many fire-detection system applications. Its combination of EN54-4 certification, a continuous 5 A output, built-in battery charger and tamper-protected enclosure make it a solid choice where regulatory compliance, reliability and straightforward installation are priorities. For projects that require a compact, compliant PSU that supports standard 2 × 7 Ah batteries and provides remote fault signalling, the HAY-PSUEN54-5A offers a balanced specification at a competitive suggested price.
Before specifying or ordering, confirm the exact enclosure variant, battery fitment and certification markings from the manufacturer datasheet, and ensure installation is carried out by a qualified engineer in accordance with EN54 and local regulations. Doing so will help ensure the PSU delivers the expected performance and compliance in your fire-safety installation.