Nittan EV-3IO Loop-Powered Addressable IO Module, 3 Inputs, 3 Outputs F16-82265
LoopPower
EV-3IO Loop-Powered IO Module
About this product
About this product
Overview
- The Nittan EV-3IO is a loop‑powered analogue addressable triple input/output interface module for Nittan Evolution addressable fire systems. It provides three Class‑B monitored inputs, three relay outputs (one mains‑rated 5 A relay and two low‑voltage 1 A relays) and an integral negative (‑ve) line short‑circuit isolator (self‑resetting).
- Supports EEPROM handheld addressing, status LEDs and remote LED outputs, and a failsafe option suitable for door‑release control.
Key benefits
- Loop‑powered — no separate supply required, simplifying wiring and installation.
- Integral negative (‑ve) line isolator maintains loop operation through a short circuit.
- Mixed relay set: one mains‑rated relay for direct control of higher voltage equipment and two low‑voltage relays for signalling/control circuits.
- Approved to EN54‑17 and EN54‑18 for loop isolation and input/output devices.
Use cases
- Interface module for addressable fire panels to monitor detector circuits and switch outputs.
- Door release control with failsafe option.
- General interface for third‑party devices requiring monitored inputs and monitored/switching outputs.
Installation & compliance
- Designed for trained/qualified fire alarm engineers; install in accordance with local regulations and relevant standards (e.g. BS 5839 where applicable).
- Meets EN54‑17 and EN54‑18. Check the manufacturer datasheet for UKCA/CE marking and certificate details.
- Refer to the product manual and datasheet for wiring diagrams, addressing procedure and limiting conditions (available from the Nittan product page).
Technical Details
Specifications
Technical-specifications
Part number
EV-3IO (F16-82265)
Operating voltage
20–38 V dc
Quiescent current
860 µA
Alarm current
8.3 mA
Isolator current (short)
≈15 mA
Inputs
3 × Class‑B monitored inputs
Outputs
1 × 5 A @ 240 Vac; 2 × 1 A @ 30 V dc
Isolator style
Negative (‑ve) line isolator (self‑resetting)
Addressing
EEPROM handheld addressing
LED indicators
Input/output, fault and isolator open; remote LED outputs
Failsafe option
Yes — suitable for door release
Standards
EN54‑17 (line isolators) and EN54‑18 (input/output devices)
Specifications
Technical-specifications
| Part number | EV-3IO (F16-82265) |
|---|---|
| Operating voltage | 20–38 V dc |
| Quiescent current | 860 µA |
| Alarm current | 8.3 mA |
| Isolator current (short) | ≈15 mA |
| Inputs | 3 × Class‑B monitored inputs |
| Outputs | 1 × 5 A @ 240 Vac; 2 × 1 A @ 30 V dc |
| Isolator style | Negative (‑ve) line isolator (self‑resetting) |
| Addressing | EEPROM handheld addressing |
| LED indicators | Input/output, fault and isolator open; remote LED outputs |
| Failsafe option | Yes — suitable for door release |
| Standards | EN54‑17 (line isolators) and EN54‑18 (input/output devices) |
EV-3IO Loop-Powered IO Module features